RENDA Nova8 Packs Eight 600W RTX PRO 6000 GPUs Into a 4U Air-Cooled Rack Server

  • Harold Fritts
  • 555 views

RENDA reports up to 54,564 tokens per second from eight liquid-cooled GPUs. The 4U system still puts about 6.4kW of heat into the room.

RENDA Nova8 Packs Eight 600W RTX PRO 6000 GPUs Into a 4U Air-Cooled Rack Server

Eight NVIDIA RTX PRO 6000 Blackwell GPUs can draw 600W apiece, making cooling a major constraint for dense AI servers. RENDA and Nexalus say their Nova8 fits those GPUs, plus a CPU, in a 4U chassis designed for a standard 19-inch air-cooled rack. Its self-contained liquid loops need no facility water piping or coolant distribution unit, but the server’s radiator still releases heat into the room unless operators choose the optional heat-export fittings.

RENDA reports a best tuned result of 54,564 tokens per second running Llama 3.3 70B Instruct. That makes the Nova8 worth a look for teams weighing GPU density against cooling changes, though the published comparison uses different hardware and serving settings. The performance figures come from the companies; they haven’t been independently audited.

Cooling stays inside the chassis

Nexalus’ jet-impingement cooling system sends coolant jets directly at hot spots on each GPU and the CPU. The approach uses cold plates over the processors, with liquid blocks occupying a single slot per GPU. RENDA and Nexalus describe the design as co-developed and jointly patented.

Ten micropumps circulate coolant through five redundant loops, while 16 fans arranged in push-pull pairs move air through the internal radiator. RENDA says the server can continue operating after a single component failure, and quick-disconnect fittings let technicians replace parts without draining the loop. The companies haven’t published throughput figures for operation with a failed pump or fan, so teams planning around redundancy will need to validate that behavior for their workloads.

The companies also say the GPUs operate more than 20°C below their maximum operating temperature. That margin may help maintain sustained workloads or tune performance for a particular model, but the figure is a vendor claim and no test conditions are provided for it.

By default, the radiator sends heat into the data centre room. Optional rear quick-connects can instead export heat as water at up to 60°C, for reuse or rejection through a dry cooler. That option changes the heat path; the standard configuration still relies on facility air handling to remove the server’s load.

Throughput figures depend on the test setup

RENDA tested Llama 3.3 70B Instruct in NVFP4 with TensorRT-LLM. The configuration used one replica per GPU, 512 concurrent requests per replica, and 256 input and 256 output tokens. With all eight GPUs capped at 600W, the best tuned run reached 54,564 tokens per second. A one-hour run averaged 53,984 tokens per second.

For the tuned runs, RENDA says it set GPU clock offsets through NVIDIA’s management tools and made no other hardware changes. The company claims up to 20% more throughput than comparable air-cooled systems and 8.6 tokens per watt, which it describes as up to 22% better efficiency in the same rack footprint.

The comparison RENDA cites is a published result of 45,527 tokens per second and 7.03 tokens per watt from a tier-one air-cooled server with eight RTX PRO 6000 Blackwell Server Edition GPUs. Nova8’s test used Workstation Edition cards. The reference system ran two EPYC CPUs, two replicas per GPU, and 8,192 concurrent users, so the results reflect different hardware and serving configurations. They don’t establish a like-for-like performance gain.

At the reported 8.6 tokens per watt, the best run implies system power of about 6.3kW. That is close to RENDA’s estimate of roughly 6.4kW at typical full load. Administrators should treat both figures as planning inputs to verify against their own workload and facility measurements.

Rack fit does not remove the power and heat burden

The Nova8 is a 4U system for a standard 19-inch rack. It combines one AMD EPYC processor, up to 2TB of DDR5 RDIMM memory, and eight U.2 PCIe Gen5 NVMe drives with four 3kW 80 PLUS Titanium power supplies in a 2+2 redundant arrangement. The EPYC model and available network options haven’t been disclosed.

The eight GPUs provide 96GB of GDDR7 memory with ECC each, or 768GB total. The system ships with Linux, NVIDIA drivers, and TensorRT-LLM installed. RENDA also lists support for vLLM, NVIDIA NIM, and other CUDA inference stacks.

For a facility, the main deployment question is where the heat goes. The Nova8 doesn’t require facility water in its standard configuration, but RENDA estimates about 6.4kW of system power at full load, which becomes heat the room’s cooling system must remove. Three servers would occupy 12U and produce roughly 19kW of heat. That may exceed the capacity of many air-cooled rows, so rack density needs to be checked against site airflow and cooling capacity before deployment.

Nexalus and RENDA haven’t published inlet temperature limits, airflow requirements, chassis dimensions, or weight. Those details matter for rack planning alongside power capacity, clearances, and the choice between room-side heat rejection and optional water heat export.

Pre-orders and remote testing

RENDA lists the Nova8 for pre-order and offers qualified organizations a remote Test Drive with access to a live server for model validation. UNICOM Engineering handles global after-sales service. RENDA is operated by Overclockers UK, part of Pro Gamers Group; Nexalus is a liquid-cooling specialist based in Cork, Ireland. Pricing and shipping dates haven’t been disclosed.

The Nova8’s practical pitch is high GPU density in a rack that lacks facility liquid cooling. Its reported throughput is a useful starting point for evaluation, but operators should confirm performance with their own models and serving settings, then account for the room heat load before sizing a deployment.

RENDA Nova8 interior with eight liquid-cooled GPUs, a Nexalus CPU cold plate, and a radiator flanked by fan wallsRENDA Nova8 4U server render with RENDA branding on the lid and a mesh front panel over four fans